In-plane flux distribution in the mix 60o- 45o T-joint of three phase transformer core
View/ Open
Date
2010-10-16Author
Dina Maizana, Maiz Ahmad
Ismail, Daut, Prof. Dr.
Rosnazri, Ali
Risnidar Chan Bahaudin, Ir.
Muhammad Irwanto
Metadata
Show full item recordAbstract
This paper describes the result of measurement of inplane
flux distribution on 100kVA 3phase distribution
transformer assembled with the mix 60o- 45o T-joint and
mitred lap corner joint with stagger yoke of 10mm. The
measurement involves the fundamental, third and fifth
harmonic of the easy and hard direction of flux density
at each location measurement. The flux distributions
have been measured using no load test by arrays of
search coil in M5 (CGO) grades material of transformer
core laminations. The localised flux density at the outer
60o-45o T-joint is 1.4T and rises to be 1.68T at the inner
edges of 60o-45o T-joint when the transformer core
energized 1.5 T 50Hz. Harmonic occurs mostly in the Tjoint
where local regions are saturated and the flux
deviates from the rolling direction.A small amount of flux
deviation from the rolling direction occurs at the overlap,
but no rotational flux is present in the joint.