dc.contributor.author | Shahanom, Uthman | |
dc.contributor.author | Ismail, Daut, Prof. Dr. | |
dc.contributor.author | Dina Maizana, Maiz Ahmad, Ir. | |
dc.date.accessioned | 2012-10-11T03:37:55Z | |
dc.date.available | 2012-10-11T03:37:55Z | |
dc.date.issued | 2010-10-16 | |
dc.identifier.isbn | 978-967-5760-03-7 | |
dc.identifier.uri | http://dspace.unimap.edu.my/123456789/21309 | |
dc.description | International Postgraduate Conference On Engineering (IPCE 2010), 16th - 17th October 2010 organized by Centre for Graduate Studies, Universiti Malaysia Perlis (UniMAP) at School of Mechatronic Engineering, Pauh Putra Campus, Perlis, Malaysia. | en_US |
dc.description.abstract | A study was conducted using sinusoidal waveform
to capture flux pattern in CRGO M5 material in a
1000kVA 11kV 3 phase transformer core. It is found
that it takes about 180⁰ electrical degree cycle for a
pool of flux to migrate from one core limb to the other
two limb. The computed and experimental values at
1.7T flux density for the core losses had shown a
difference of 4.2 %. There are two loops of flux flow
exist at any phase( ωt) angle in the core. The hotspot
area of the core is near the inner core of the T joint
and along the core window. The 2D FEM software
used has satisfied and fulfill the objective of the work
interest. | en_US |
dc.language.iso | en | en_US |
dc.publisher | Universiti Malaysia Perlis (UniMAP) | en_US |
dc.relation.ispartofseries | Proceedings of the International Postgraduate Conference on Engineering (IPCE 2010) | en_US |
dc.subject | Sinusoidal waveform | en_US |
dc.subject | Transformer losses | en_US |
dc.subject | T-Joint | en_US |
dc.title | Flux pattern in 1000 kVA 11/.433 kV distribution transformer core to sinusoidal wave | en_US |
dc.type | Working Paper | en_US |
dc.publisher.department | Centre for Graduate Studies | en_US |
dc.contributor.url | shah@mtm.com.my | en_US |
dc.contributor.url | ismail.daut@unimap.edu.my | en_US |
dc.contributor.url | dina@unimap.edu.my | en_US |