Comparison of losses and flux distribution in 3 phase 100 kVA distribution transformers assembled from various type of T-Joint geometry
View/ Open
Date
2006Author
Ismail, Daut
Dina Maizana, Maiz Ahmad
Shuhaimi, Zakaria
S. Uthman
Soib, Taib
Metadata
Show full item recordAbstract
This paper describes results of an investigation of the variation of power loss, building factor, flux leakage and flux distribution in 3-phase model transformer cores assembled from various type of T-joint geometry. The loss of the core with T-joint 60° was 10%, 12% and 15% better than the
core with T-joint 45°, T-joint 23° and T-joint 90° respectively and 1.7 T, 50 Hz. The flux lines showed that flux penetration into the central limb was an important factor in causing the differences in performance.