Performance of thermal electric cooling (TEC) air condition for a small office space
View/ Open
Date
2021-08Author
Muhammad Syahril, Abd Aziz
Shamsul Anuar, Shamsudin
Mohd Farid, Ismail
Mohd Nizam, Sudin
Huthaifa Ahmad Al-Issa
Metadata
Show full item recordAbstract
An experimental investigation on the TEC (thermoelectric cooler) air-conditioner with evaporative cooler that acts as condensing unit in a small office space was performed. Various engineering performance criteria of the system such as the Coefficient of
Performance (COP) of the TEC plate, the COP of the developed product, the COP of evaporative cooler and the sound level of the product were evaluated. The tested area office size was 12 ft × 11 ft, used for light activities and with few equipment generating heat. As a result, the TEC air conditioner by evaporative cooling was developed that consists of several parts that include thermoelectric modules model TEC-12706, heatsink fan, water heatsink, water pump, water pipeline, radiator, and evaporative cooler. This experiment found that the COP of the TEC plates condensed by evaporative cooling is 0.39.
The optimum running current for the system is 5 A when the system’s COP achieved the highest values which is 1.7. The COP of the evaporative cooling decreases with the increment of the current supply to the TEC. Consequently, the 62.9 dB sound level of the system is acceptable.